Search Exchange
Search All Sites
Nagios Live Webinars
Let our experts show you how Nagios can help your organization.Login
Directory Tree
Directory
whit
bywhit, August 19, 2011
Used iReasoning's MIB browser to get the values to use (http://www.ireasoning.com/downloadmibbrowserfree.php). After some trial and error, this works for the internal sensor:
./check_snmp_temperature.pl -H -C public -n internat-tempf.0 -d .1.3.6.1.4.1.20916.1.7.1.1.1.2.0 -i 100F -o F -a tempf -w 85 -c 90
and this works for the external we've attached:
./check_snmp_temperature.pl -H -C public -n digital-sen1-2.0 -d .1.3.6.1.4.1.20916.1.7.1.2.1.2.0 -i 100F -o F -a sen1-2 -w 85 -c 90
./check_snmp_temperature.pl -H -C public -n internat-tempf.0 -d .1.3.6.1.4.1.20916.1.7.1.1.1.2.0 -i 100F -o F -a tempf -w 85 -c 90
and this works for the external we've attached:
./check_snmp_temperature.pl -H -C public -n digital-sen1-2.0 -d .1.3.6.1.4.1.20916.1.7.1.2.1.2.0 -i 100F -o F -a sen1-2 -w 85 -c 90