check_ups_health

Rating
0 votes
Favoured:
0
Compatible With
  • Nagios 1.x
  • Nagios 2.x
  • Nagios 3.x
  • Nagios 4.x
  • Nagios XI
Owner
Hits
21260
Nagios CSP

Meet The New Nagios Core Services Platform

Built on over 25 years of monitoring experience, the Nagios Core Services Platform provides insightful monitoring dashboards, time-saving monitoring wizards, and unmatched ease of use. Use it for free indefinitely.

Monitoring Made Magically Better

  • Nagios Core on Overdrive
  • Powerful Monitoring Dashboards
  • Time-Saving Configuration Wizards
  • Open Source Powered Monitoring On Steroids
  • And So Much More!
check_ups_health is a plugin which was designed to monitor a broad range of ups models. Instead of installing many plugins for many types of devices, one is enough. Implemented are APC, Merlin Gerin, Socomec and Standard UPS Mibs.
Running the modes uptime, hardware-health, battery-health

apc/mge-galaxy-5500
OK - device is up since 1d 5h 53m 4s | 'uptime'=1793;15:;5:;;
OK - hardware working fine, at least i hope so, because self-tests were never run
OK - battery status is batteryNormal, capacity is 100.00%, output load 49.00%, temperature is 16.00C, remaining battery run time is 19.00min | 'capacity'=100%;25:;10:;0;100 'output_load'=49%;75;85;0;100 'battery_temperature'=16;70;80;; 'remaining_time'=19;10:;8:;; 'input_frequency'=50;;;;

apc/smart-ups-rt-10000-rm-xl
OK - device is up since 5d 3h 7m 25s | 'uptime'=7387;15:;5:;;
CRITICAL - last selftest was 314 days ago (Mon Dec 2 00:00:00 2013), selftest result was ok | 'selftest_age'=314.97;28;28;;
OK - battery status is batteryNormal, capacity is 100.00%, output load 26.00%, temperature is 25.00C, remaining battery run time is 56.00min | 'capacity'=100%;25:;10:;0;100 'output_load'=26%;75;85;0;100 'battery_temperature'=25;70;80;; 'remaining_time'=56;10:;8:;; 'input_voltage'=241;;;; 'input_frequency'=49;;;; 'output_voltage'=228;;;; 'output_frequency'=50;;;;

apc/smart-ups-rt-1000-rm-xl
OK - device is up since 4d 21h 16m 52s | 'uptime'=7037;15:;5:;;
CRITICAL - last selftest was 300 days ago (Mon Dec 16 00:00:00 2013), selftest result was ok | 'selftest_age'=300.97;28;28;;
OK - battery status is batteryNormal, capacity is 100.00%, output load 0.00%, temperature is 18.00C, remaining battery run time is 113.00min | 'capacity'=100%;25:;10:;0;100 'output_load'=0%;75;85;0;100 'battery_temperature'=18;70;80;; 'remaining_time'=113;10:;8:;; 'input_voltage'=230;;;; 'input_frequency'=50;;;; 'output_voltage'=228;;;; 'output_frequency'=50;;;;

apc/smart-ups-vt-20-kva
OK - device is up since 52d 16h 7m 55s | 'uptime'=75848;15:;5:;;
CRITICAL - last selftest was 313 days ago (Tue Dec 3 00:00:00 2013), selftest result was ok | 'selftest_age'=313.97;28;28;;
OK - battery status is batteryNormal, capacity is 100.00%, output load 56.00%, temperature is 23.00C, remaining battery run time is 25.00min | 'capacity'=100%;25:;10:;0;100 'output_load'=56%;75;85;0;100 'battery_temperature'=23;70;80;; 'remaining_time'=25;10:;8:;; 'input_voltage'=230;;;; 'input_frequency'=49;;;; 'output_voltage'=231;;;; 'output_frequency'=49;;;;

apc/smart-ups-vt-40-kva
OK - device is up since 52d 16h 16m 6s | 'uptime'=75856;15:;5:;;
CRITICAL - last selftest was 313 days ago (Tue Dec 3 00:00:00 2013), selftest result was ok | 'selftest_age'=313.97;28;28;;
OK - battery status is batteryNormal, capacity is 100.00%, output load 33.00%, temperature is 22.00C, remaining battery run time is 38.00min | 'capacity'=100%;25:;10:;0;100 'output_load'=33%;75;85;0;100 'battery_temperature'=22;70;80;; 'remaining_time'=38;10:;8:;; 'input_voltage'=230;;;; 'input_frequency'=50;;;; 'output_voltage'=231;;;; 'output_frequency'=50;;;;

merlingerin/comet-extreme-12kva
OK - device is up since 337d 2h 22m 59s | 'uptime'=485423;15:;5:;;
OK - hardware working fine. no alarms
OK - battery ok, capacity is 100.00%, remaining battery run time is 51.50min, output load1 30.00% | 'capacity'=100%;25:;10:;0;100 'remaining_time'=51.50;15:;10:;; 'input_voltage1'=219.60;;;; 'input_frequency1'=50;;;; 'input_current1'=9.20;;;; 'output_load1'=30%;75;85;0;100 'output_voltage1'=230;;;; 'output_frequency1'=50;;;; 'output_current1'=8.50;;;;

socomec/netvision
OK - device is up since 229d 15h 41m 45s | 'uptime'=330702;15:;5:;;
OK - found 0 alarms
OK - battery status is batteryNormal, capacity is 100.00%, temperature is 24.00C, output load1 47.00%, output load2 42.00%, output load3 28.00% | 'capacity'=100%;25:;10:;0;100 'battery_temperature'=24;35;38;; 'remaining_time'=-1;0;0;; 'input_frequency'=50;;;; 'input_voltage1'=234;;;; 'input_voltage2'=235;;;; 'input_voltage3'=235;;;; 'output_frequency'=50;;;; 'output_load1'=47%;75;85;0;100 'output_voltage1'=229;;;; 'output_load2'=42%;75;85;0;100 'output_voltage2'=230;;;; 'output_load3'=28%;75;85;0;100 'output_voltage3'=229;;;;

socomec/netys-rt
OK - device is up since 23d 16h 37m 23s | 'uptime'=34117;15:;5:;;
OK - temperature 32C, no alarms | 'temperature'=32;;;;
OK - output source is normal, battery condition is good, charging, capacity is 100.00%, output load1 0.00%, temperature is 32.00C, remaining battery run time is 888.00min | 'capacity'=100%;25:;10:;0;100 'output_load1'=0%;75;85;0;100 'battery_temperature'=32;35;38;; 'remaining_time'=888;15:;10:;; 'input_voltage1'=234;;;; 'input_frequency1'=49.90;;;; 'output_voltage1'=229;;;; 'output_frequency'=49.90;;;;